DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si
555-230-127
Issue 1
August 1997
Maintenance Object Repair Procedures
Page 10-518DS1-BD (DS1 Interface Circuit Pack)
10
DS1 Board Loopback Test (#1209)
This test is destructive.
The DS1 Board Loopback (BLB) Test causes a loopback at the TN767E DS1
board edge and tests DS1 board internal circuitry.
The test is destructive and can only be initiated by a system technician
demanded
t
est ds1-loop PCSS ds1/csu-loopback-tests command.
All trunks or ports on the DS1 Interface circuit pack must be busied out via the
system technician busyout board command before running the BLB Test.
When the BLB Test is initiated, maintenance software sends an appropriate
message to the TN767E DS1 Interface circuit pack to start the test. The board will
set up the BLB loopback, transmit a test pattern, and verify that the pattern is
received unaltered through the loopback. If the transmitted and received pattern
is different, the test fails.
When the test is complete, all trunks or ports on the TN767E DS1 Interface circuit
pack are restored to the in-service state after the release board command is
entered
Table 10-174. TEST #1209 DS1 Board Loopback Test
Error
Code
Test
Result Description/ Recommendation
ABORT Internal system error
1. Retry
t
est ds1-loop PCSS ds1/csu-loopback-tests at 1-minute intervals a
maximum of 5 times.
1005 ABORT DS1 Board Loopback Test cannot be executed in the current configuration. To
run this Test, the TN767E or later suffix DS1 must be administered for
24-channel operation. The "Bit Rate" field on the DS1 circuit pack administration
form must be set to "1.544" for 24-channel operation.
1015 ABORT Ports on the DS1 Interface circuit pack have not been busied out to
out-of-service.
1. Enter busyout board PCSS to put all trunks or ports of the DS1 Interface
circuit pack into the out-of-service state.
2. Retry the command.
Continued on next page