DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si
555-230-127
Issue 1
August 1997
Maintenance Object Repair Procedures
Page 10-1097RING-GEN (Analog Ring Generator)
10
Hardware Error Log Entries and Test to Clear
Values
System Technician-Demanded Tests:
Descriptions and Error Codes
Always investigate tests in the order presented in the following tables when
inspecting errors in the system. By clearing error codes associated with the
Analog Ring Generator Initialization Test
, for example, you may also clear errors
generated from other tests in the testing sequence.
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
1. D = Destructive; ND = Nondestructive
Analog Ring Generator Error Log Entries
Error
Type
Aux
Data Associated Test
Alarm
Level
On/Off
Board Test to Clear Value
0
1
0 Any Any Any test environment UU
1 Analog Ring Generator Query
Test (#118)
MAJOR ON test environment UU r 3
Multicarrier Cabinet
Order of Investigation
Short Test
Sequence
Long Test
Sequence D/ND
1
Analog Ring Generator Initialization Test (#117) X X ND
Analog Ring Generator Query Test (#118) X X ND
Battery & Battery Charger Query Test (#5) (a) X X ND
AC Power Query Test (#78) (b) X X ND
Power Unit Query Test (Carrier E) (#127) (c) X X ND
Power Unit Query Test (Carrier D) (#127) (c) X X ND
Power Unit Query Test (Carrier A) (#127) (c) X X ND
Power Unit Query Test (Carrier B) (#127) (c) X X ND
Power Unit Query Test (Carrier C) (#127) (c) X X ND
Emergency Transfer Query Test (#124) (d) X X ND
Cabinet Sensors Query Test (#122) (e) X X ND
External Alarm Lead Query Test (#120) (f) X X ND