Maintenance Object Repair Procedures
Page 10-975PI-SCI (System Communication Interface)
10
Error Log Entries and Test to Clear Values
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
2. See WARNING below.
!
WARNING:
The "test interface long" command resets the PI-BD and causes all ISDN-PRI and
BX.25 links to come down.
3. Major alarms may be downgraded to Warning alarms based on the value used in the set options
command.
Table 10-331. PI-SCI System Communication Interface Error Log Entries
Error
Type
Aux
Data Associated Test Alarm Level
On/Off
Board Test to Clear Value
0
1
0 Any Any Any test interface PCS sh r 1
1 (a) 2055
2056
2057
2058
none none none none
257 (b) Any none MAJOR ON test interface PCS l
2
769 (c) Any none MAJOR/
WARNING
3
OFF test interface PCS l
2
1025 (d) Any none MAJOR/
WARNING
3
OFF test interface PCS l
2
1281 (e) Any Sci Start Test (#176) MAJOR/
WARNING
3
OFF test interface PCS l
2
1793 (f) Any none MAJOR ON test interface PCS l
2
2049 (g) 90xx Sci Start Test (#176) MAJOR ON test interface PCS l
2
2305 (f) Any Sci Self Test (#231) MAJOR ON test interface
PCS sh r 2
2561 (h) Any none MAJOR/
WARNING
3
OFF test interface PCS l
2
2817 (i) Any none MAJOR/
WARNING
3
OFF test interface PCS l
2
2818 (j) Any none MAJOR/
WARNING
3
OFF test interface PCS l
2
3073 (f) Any none MAJOR/
WARNING
3
OFF test interface PCS l
2