Page 10-1136SHDW-LNK (Memory Shadowing Link)
10
2048
(cont’d.)
FAIL Refer to Chapter 6 to understand how to correctly replace the
Duplication-Interface circuit pack.
If none of the four red LEDs are on AND if this is the first attempt to
clear the problem, replace the Standby SPE Processor circuit pack as
described in Chapter 6 and proceed with Steps 9, 10, and 11.
If none of the four red LEDs are on AND if this is the second attempt to
clear the problem (that is, the Standby SPE Processor circuit pack has
already been replaced), replace the Standby SPE Memory circuit pack
as described in Chapter 6 and proceed with Steps 9, 10, and 11.
If none of the four red LEDs are on AND if this is the third attempt to
clear the problem (that is, the Standby SPE Processor and Standby
SPE Memory circuit packs have already been replaced), replace the
Standby SPE Duplication Interface circuit pack as described in
Chapter 6 and proceed with Steps 9, 10, and 11.
If none of the four red LEDs are on AND if this is the fourth attempt to
clear the problem (that is, the Standby SPE Processor, Standby SPE
Memory, and Standby SPE Duplication Interface circuit packs have
already been replaced), replace the Active SPE Duplication Interface
circuit pack as described in Chapter 6 and proceed with Steps 9, 10,
and 11.
NOTE:
The Duplication Interface circuit pack must be made to reside in the
Standby SPE before it can be replaced.
Table 10-406. TEST #318 Shadow Link Test — Continued
Error
Code
Test
Result Description/ Recommendation
Continued on next page