DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si
555-230-127
Issue 1
August 1997
Maintenance Object Repair Procedures
Page 10-327CO-TRK (CO Trunk)
10
2056 ABORT An error occurred while trying to obtain results from the TN771 circuit
pack.
1. Test the TN771 circuit packs.
2. If the test continues to abort escalate the problem.
FAIL Measured transmission performance was in the unacceptable range as
administered on the trunk group form. Retrieve a measurement report via
the list testcalls command. Make sure that ATMS thresholds are set
properly on page 4 of the trunk group form. Besides the facility, test
failures can be caused by faulty test lines or switch paths. If the
measurements point to a facility problem, report the results to the trunk
vendor.
8000 FAIL Measured transmission performance was in the marginal range as
administered on the trunk group form. This generally means that the trunk
is usable but has an undesirable amount of noise or loss. If the user does
not report unacceptable effects, it may not be necessary to take any
action. Retrieve a measurement report via the list testcalls command.
Make sure that ATMS thresholds are set properly on page 4 of the trunk
group form.
Table 10-106. TEST #844-848 Transmission Test — Continued
Error
Code
Test
Result Description/ Recommendation
Continued on next page