DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si
555-230-127
Issue 1
August 1997
Maintenance Object Repair Procedures
Page 10-1040PR-MAINT (Maintenance Processor [TN790 RISC Systems])
10
1000 ABORT System software resources required for this test are not available.
1. Retry at 1-minute intervals a maximum of 5 times.
1050 ABORT System could not determine if the testing of the INADS port is
administered.
1. Enter the change system-parameters maintenance command. Verify
that the ‘‘Test Remote Access Port?’’ field is set to ‘‘y.’’
2. Retry the command at 1-minute intervals a maximum of 5 times.
2500 Internal system error
2033 Could not send MTP message.
1. Retry at 1-minute intervals a maximum of 5 times.
2000 ABORT MTP did not respond to the test request.
1. Repeat the test at 1-minute intervals a maximum of 5 times.
2. If all MTP tests are aborting, execute the test processor a/b long
command in order to reset MTP and to examine the results of the MTP
Reset Test (#101).
3. Replace the Processor circuit pack.
4. If only the MTP outpulse relay test is aborting, escalate problem.
FAIL MTP reported test failure. No loop current detected. The following steps
apply to either an internal or external modem ( Some additional steps
apply to an external modem only).
1. Retry at 1-minute intervals a maximum of 5 times.
2. For an external modem, if the test continues to fail:
a. If Test #230 failed, use the external modem recommendations
listed in Test #230.
b. If Test #230 passes, the MTP most likely received a NO DIAL TONE
response to the ATD command sent from the MTP. This problem is
between the modem and the INADS trunk.
3. Examine the INADS trunk for connectivity, and manually check for loop
current.
4. If there is no INADS trunk, this test should be disabled. To disable the
test, issue the change system-parameters maintenance command,
and change the Test Remote Access Port field to ‘‘n.’’
5. If the INADS trunk checks out okay, but the test still fails, check the
backplane connector wiring.
6. If the backplane wiring checks out okay, replace the Processor circuit
pack.
Table 10-355. TEST #102 MTP Outpulse Relay Test Continued
Error
Code Test Result Description/ Recommendation
Continued on next page