Page 10-556DUPINT (Duplication Interface Circuit Pack)
10
Error Log Entries and Test to Clear Values
Notes:
a. This error indicates that an unexpected hardware reset has occurred on
the Duplication Interface circuit pack. Appropriate action has been taken
by the software to prevent malfunction. However, if this type error occurs
with regular frequency, the DUPINT circuit pack may need to be replaced.
b. There are several possible Aux Data fields for this error, including blank.
All indicate loss of contact with the indicated Duplication Interface circuit
packs. The following table summarizes the Aux Data fields.
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
Table 10-185. Duplication Interface Circuit Pack Error Log Entries
Error
Type
Aux
Data Associated Test
Alarm
Level
On/Off
Board Test to Clear Value
0
1
0 Any Any Any test dup 1C sh r 1
1 Sanity Circuit Test (#273) MAJOR/
WRN
ON test dup 1C l r 1
108 (a) Any None
109 (a) Any None
257 SAT Loop Back Test (#274) MAJOR/
WRN
ON test dup 1C sh r 3
513 SPE A Loop Back Test (#275) MAJOR/
WRN
ON test dup 1C sh r 3
769 SPE B Loop Back Test (#276) MAJOR/
WRN
ON test dup 1C sh r 3
1025 Sanity Maze Test (#277) MAJOR
/WRN
ON test dup 1C sh r 3
1281 (b) Any Dupint Status Query Test (#315) MAJOR/
WRN
ON test dup 1C sh r 6
1537 (c) Any Background Test Query Test
(#271)
MAJOR/
WRN
ON test dup 1C sh r 3
1793 (d) Any MBUS Time-Out Query Test
(#285)
MAJOR/
WRN
ON test dup 1C l r 3
2049 Inter-Dupint Loop Around Test
(#280)
MAJOR/
WRN
ON test dup 1C sh r 3