Page 10-667FL-DATA (Flash Data Consistency)
10
68 FAIL The update files and load vintages are different in both SPEs. The
Standby SPE has the most current update file.
69 FAIL The update files, load vintages, and translations are different in both
SPEs. The Standby SPE has the most current update file, and the
Active SPE has the most current translations.
70 FAIL The update files, load vintages, and translations are different in both
SPEs. The Standby SPE has the most current update file and
translations.
1. Follow the procedures for Error Code 4 to get the correct load
vintage. After running the test card-mem long command, check
for Error Codes 32 or 64. Follow the recovery procedure under the
applicable error code.
72 FAIL The update files and announcements are different in both SPEs. The
Standby SPE has the most current update file and the Active SPE has
the most current announcements.
1. Issue the save announcements command to save
announcements on both SPEs.
2. Follow the procedures for Error Code 64.
73 FAIL The update files, translations, and announcements are different in both
SPEs. The Active SPE has the most current translations and
announcements, and the Standby SPE has the most current update
file.
74 FAIL The update files, translations, and announcements are different in both
SPEs. The Active SPE has the most current announcements, and the
Standby SPE has the most current update file and translations.
1. Issue the save translations command.
2. Issue the save announcements command.
3. Follow the procedures for Error Code 64.
Table 10-223. TEST #421 Flash Data Consistency Check Test — Continued
Error Code
Test
Result Description/Recommendation
Continued on next page