DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si
555-230-127
Issue 1
August 1997
Maintenance Object Repair Procedures
Page 10-1139SHDW-LNK (Memory Shadowing Link)
10
2049
(cont’d.)
FAIL
(cont’d.)
8. Issue the display errors command and check to see if an Error Type 58 is
logged against STBY-SPE. If an Error Type 58 is logged OR if no error
types are logged against STBY-SPE, the problem is either the Standby
SPE Processor circuit pack, or the Standby SPE Memory circuit pack, or
the carrier B Duplication-Interface circuit pack, or the carrier A
Duplication-Interface circuit pack.
If the red LED on the Standby SPE Processor circuit pack is on and the
Standby SPE Processor circuit pack has not been replaced yet,
replace the Standby SPE Processor circuit pack as described in
Chapter 6 and proceed with Steps 9, 10, and 11. If the red LED on the
Standby SPE Processor circuit pack is on and the Standby SPE
Processor circuit pack has been replaced, replace the Standby SPE
Memory circuit pack as described in Chapter 6 and proceed with
Steps 9, 10, and 11.
If the red LED on the Standby SPE Memory circuit pack is lit, replace
the Standby SPE Memory circuit pack as described in Chapter 6 and
proceed with Steps 9, 10, and 11.
If the red LED on the Standby SPE Duplication Interface circuit pack is
lit, replace the Standby SPE Duplication Interface circuit pack as
described in Chapter 6 and proceed with Steps 9, 10, and 11.
If the red LED on the Active SPE Duplication Interface circuit pack is lit,
replace the Active SPE Duplication Interface circuit pack as described
in Chapter 6 and proceed with Steps 9, 10, and 11.
NOTE:
The Duplication Interface circuit pack must be made to reside in the
Standby SPE before it can be replaced.
Table 10-406. TEST #318 Shadow Link Test — Continued
Error
Code
Test
Result Description/ Recommendation
Continued on next page