DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si
555-230-127
Issue 1
August 1997
Maintenance Object Repair Procedures
Page 10-1268TAPE-DAT (Tape Consistency)
10
36 FAIL The update files and load vintages are different in both SPEs. The Active
SPE has the most current update file.
37 FAIL The update files, load vintages, and translations are different in both SPEs.
The Active SPE has the most current update file and translations.
38 FAIL The update files, load vintages, and translations are different in both SPEs.
The Active SPE has the most current update file, and the Standby SPE had
the most current translations.
1. Follow the procedures for Error Code 4 to get the correct load vintage.
After running the test tape long command, check for Error Code #32
or #64. Follow the recovery procedure under the applicable error code.
40 FAIL The update files and announcements are different in both SPEs. The Active
SPE has the most current update file and announcements.
1. Issue the save announcements command to save announcements on
both SPEs.
2. Have INADS issue the copy update-file command to copy the update
file from the Active to the Standby SPE.
3. Issue the test tape long command again to resolve the alarms.
41 FAIL The update files, translations, and announcements are different in both
SPEs. The Active SPE has the most current update file, translations, and
announcements.
42 FAIL The update files, translations, and announcements are different in both
SPEs. The Active SPE has the most current update file and
announcements, and the Standby SPE has the most current translations.
1. Issue the save translations command.
2. Issue the save announcements command.
3. Have INADS issue the copy update-file command to copy the update
file from the Active to the Standby SPE.
4. Reissue the test tape long command to resolve the alarms.
Table 10-437. TEST #421 Tape Data Consistency Check Test — Continued
Error
Code
Test
Result Description/ Recommendation
Continued on next page