Lucent Technologies lucent Server User Manual


  Open as PDF
of 2392
 
DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si
555-230-127
Issue 1
August 1997
Maintenance Object Repair Procedures
Page 10-902OPS-LINE (DS1 OPS Line)
10
Audit and Update Test (#36)
This test sends port level translation data from switch processor to the DS1
Interface circuit pack to assure that the trunk’s translation is correct. Translation
updates include the following data: trunk type (in/out), dial type, timing
FAIL
(con’t.)
6. Replace the circuit pack.
NOTE:
If the conference circuit test fails for all ports on a circuit pack, a
-5 volt power problem is indicated. If a TN736 or TN752 power
unit circuit pack is present, either the 631DB AC power unit or
the 676B DC power unit may be defective. (The 631DB power
unit is used in a medium cabinet powered by an AC source. The
645B power unit is used in a medium cabinet powered by a DC
power source.) The system may contain a TN736 or TN752
power unit or a 631DB AC power unit, but not both types of
power units. To investigate problems with a 631DB AC power
unit, refer to the CARR-POW (carrier port power unit for
AC-powered systems) Maintenance documentation. To
investigate problems with a 645B DC power unit, refer to the
CARR-POW (carrier port power unit for DC-powered systems)
Maintenance documentation. If a red LED on TN736 or TN752
power unit circuit pack is on, replace the pack.
PASS The port can correctly conference multiple connections. User-reported
troubles on this port should be investigated using other port tests and
by examining station, trunk, or external wiring.
0NO
BOARD
The test could not relate the internal ID to the port (no board). This
could be due to incorrect translations, no board is inserted, an incorrect
board is inserted, or an insane board is inserted.
1. Check to ensure that the board translations are correct. Use the list
config command, and resolve any problems that are found.
2. If the board was found to be correctly inserted in step 1, issue the
busyout board command.
3. Issue the reset board command.
4. Issue the release busy board command.
5. Issue the test board long command. This should re-establish the
linkage between the internal ID and the port. If this is not the case,
dispatch to check to ensure that there is a valid board inserted.
Table 10-304. TEST #7 Conference Circuit Test — Continued
Error
Code
Test
Result Description/ Recommendation
Continued on next page