DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si
555-230-127
Issue 1
August 1997
Maintenance Object Repair Procedures
Page 10-855MMI-LEV (Multimedia Interface Resource Level)
10
by failing the Archangel sanity scan test or is removed from service physically by
removing the circuit pack from the carrier, no error/alarm is raised against either
the MMI-BD or the MMI-PT maintenance objects. Therefore, if a MMI-LEV
error/alarm exists, yet no alarms have been raised against MMI-BD or MMI-PT
maintenance objects, a MMI circuit pack may have been removed from service
causing the MMI-LEV error/alarm. To resolve a MMI-LEV MAJOR alarm, restore
the number of MMI ports available for service to be equal to or greater than the
calculated port capacity.
To determine how many MMI circuit packs are needed for the MMCH feature:
1. Using the display system-parameters maintenance command, locate
the number listed in the Minimum Maintenance Thresholds
(MMIs)
field and record this number.
2. Use the list configuration
command to verify the number of MMI ports.
3. Compare this number with the value listed in the MMI field on the
System-Parameters Maintenance form (number listed in step 1 a minimum
thresholds number for MMI ports of between 0-128). Each MMI circuit
pack contains a maximum of 32 ports. If the number in the MMIs field is
less than or equal to 32, one MMI circuit pack is needed. If this number is
64, then two MMI circuit pack are needed.
4. Use the list configuration command to verify that the number of MMI
circuit packs listed agrees with the required minimum port capacity (from
step 1). If the number of MMI circuit packs listed in the step 2 differs from
the calculated number, restore the number of MMI circuit packs to the
correct value, in order to resolve the MMI-LEV alarm.
Error Log Entries and Test to Clear Values
To resolve this alarm, correct the out-of-service problem by following these procedures:
1. See “MMI-PT” and “MMI-BD” and resolve any associated alarms.
1. The number of MMI resources in the system that are in service has fallen below the calculated
minimum value. If the number of in-service MMI ports falls below the MMCH port capacity (value
entered in the Minimum Maintenance Thresholds for MMIs
field) on the System-Parameters
Maintenance form, a MMI-LEV error is logged. If this outage continues for 15 minutes, a MAJOR
alarm is raised.
Table 10-287. MMI-LEV Error Log Entries
Error
Type
Aux
Data Associated Test Alarm Level
On/ Off
Board Test to Clear Value
1
1
Any None MAJOR OFF