DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si
555-230-127
Issue 1
August 1997
Maintenance Object Repair Procedures
Page 10-12AC-POWER
10
The environment maintenance strategy to be used depends on both the cabinet
configuration and the type of powering. Refer to the "DC-POWER (Single-Carrier
Cabinet Power)" information for environment maintenance strategy.
In a DC-powered multicarrier cabinet system, the AC-POWER maintenance
object still exists, but serves no functional purpose. Because the system cannot
determine the type of powering provided, all AC-POWER tests should always
either pass or abort.
Error Log Entries and Test to Clear Values
System Technician-Demanded Tests:
Descriptions and Error Codes
Always investigate tests in the order presented in the following table. By clearing
error codes associated with the
AC Power Query Test
, for example, you may also
clear errors generated from other tests in the testing sequence.
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
Table 10-5. AC Power Error Log Entries
Error
Type
Aux
Data Associated Test
Alarm
Level
On/Off
Board Test to Clear Value
0
1
0 Any Any Any test environment P sh r 1
513 Any AC Power Query Test
(#78)
WARNING OFF test environment P sh r 1
Table 10-6. System Technician-Demanded Tests: AC-Power
Order of Investigation
Short Test
Sequence
Long Test
Sequence D/ND
1
Battery & Battery Charger Query Test (#5) (a) X X ND
AC Power Query Test (#78) X X ND
Power Unit Query Test (carrier E) (#127) (b) X X ND
Power Unit Query Test (carrier D) (#127) (b) X X ND
Power Unit Query Test (carrier A) (#127) (b) X X ND
Power Unit Query Test (carrier B) (#127) (b) X X ND
Continued on next page