DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si
555-230-127
Issue 1
August 1997
Maintenance Object Repair Procedures
Page 10-690HYB-LINE (Hybrid Line)
10
Hybrid Line Remote Digital Loop Around Test
(#59)
This test checks the digital control pair from the port circuit to the terminal. The
on-board microprocessor sends a message to the terminal and checks for a
proper return message. This test is repeated three times, with two out of the three
attempts passing being sufficient for this test to pass. [G1] This test will run if the
station is in-service or out-of-service.
0NO
BOARD
The test could not relate the internal ID to the port (no board). This could
be due to incorrect translations, no board is inserted, an incorrect board is
inserted, or an insane board is inserted.
1. Check to ensure that the board translations are correct. Use the list
config command, and resolve any problems that are found.
2. If the board was found to be correctly inserted in step 1, issue the
busyout board command.
3. Issue the reset board command.
4. Issue the release busy board command.
5. Issue the test board long command. This should re-establish the
linkage between the internal ID and the port. If this is not the case,
dispatch to check to ensure that there is a valid board inserted.
Table 10-230. TEST #59 Hybrid Line Remote Digital Loop Around Test
Error
Code
Test
Result Description/ Recommendation
ABORT Internal System Error.
1. Retry the command at 1-minute intervals for a maximum of 5 times.
2. If the test continues to abort, escalate the problem.
Continued on next page
Table 10-229. TEST #58 Hybrid Line Local Digital Loop Around Test — Continued
Error
Code
Test
Result Description/ Recommendation
Continued on next page