DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si
555-230-127
Issue 1
August 1997
Maintenance Object Repair Procedures
Page 10-285CO-DS1 (DS1 CO Trunk)
10
Notes:
a. Error Type 1Aux Data 57408—No tip ground is detected on an outgoing
call.
Aux Data 57487—PBX could not get "loop close" signal (TN767).
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the appropriate
test description and follow the recommended procedures.
2. This alarm will only be raised when the System-Parameter Country form has the Base Tone Generator
field set to 4 (Italy). This alarm will be a MINOR alarm unless 75% or more trunks in this trunk group are
out of service, then the alarm will be upgraded to a MAJOR alarm.
3. Minor alarms on this maintenance object (MO) may be downgraded to Warning alarms based on the
values used in the set options command. If the Minor alarm is not downgraded by the set options
values, the Minor alarm is upgraded to a Major alarm if 75 percent of the trunks in this group are
alarmed.
1 (a) 57408
1 (a) 57487
15 (b) Any Port Audit and
Update Test (#36)
18 (c) 0 busyout trunk
<grp>/<mbr>
WARNING OFF release trunk
<grp>/<mbr>
130 (d) None WARNING ON test trunk <grp>/<mbr>
257 (e) 57392 DS1 CO Dial Tone
Seizure Test (#314)
MIN/MAJ
2
OFF
513 (f) 57393 DS1 CO Dial Tone
Seizure Test (#314)
MIN/MAJ
2
OFF
769 (g) 57484
1025 DS1CO Dial Tone
Seizure Test (#314)
WARNING OFF test trunk <grp>/<mbr>
1281 Conference Circuit
Test (#7)
MAJ/MIN/
WRN
3
ON test trunk <grp>/<mbr> r
4
1537 NPE Crosstalk Test
(#6)
MAJ/MIN/
WRN
3
ON test trunk <grp>/<mbr> r
3
1793 (h) ON test board PCSS l
2562(i)) 16665
2817(j) 52992
3840 (k) Port Audit and
Update Test (#36)
Table 10-94. DS1 CO Trunk Error Log Entries — Continued
Error
Type
Aux
Data Associated Test
Alarm
Level
On/Off
Board Test to Clear Value
Continued on next page