DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si
555-230-127
Issue 1
August 1997
Maintenance Object Repair Procedures
Page 10-664FL-DATA (Flash Data Consistency)
10
38 FAIL The update files, load vintages, and translations are different in both
SPEs. The Active SPE has the most current update file, and the
Standby SPE has the most current translations.
1. Follow the procedures for Error Code 4 to get the correct load
vintage. After running the test card-mem long command, check
for Error Codes 32 or 64. Follow the recovery procedure under the
applicable error code.
40 FAIL The update files and announcements are different in both SPEs. The
Active SPE has the most current update file and announcements.
1. Issue the save announcements command to save
announcements on both SPEs.
2. Have INADS issue the copy update-file command to copy the
update file from the Active to the Standby SPE.
3. Run the test card-mem long again to resolve the alarms.
41 FAIL The update files, translations, and announcements are different in both
SPEs. The Active SPE has the most current update file, translations,
and announcements.
42 FAIL The update files, translations, and announcements are different in both
SPEs. The Active SPE has the most current update file and
announcements, and the Standby SPE has the most current
translations.
1. Issue the save translations command.
2. Issue the save announcements command.
3. Have INADS issue the copy update-file command to copy the
update file from the Active to the Standby SPE.
4. Reissue the test card-mem long command to resolve the alarms.
Table 10-223. TEST #421 Flash Data Consistency Check Test — Continued
Error Code
Test
Result Description/Recommendation
Continued on next page