Page 10-1026POWER (Battery & Battery Charger) for AC-Powered Systems
10
Battery & Battery Charger Query Test (#5)
This test queries the Maintenance/Tape Processor in a multicarrier cabinet PPN
system without High or Critical Reliability, the Duplication Interface circuit pack in
a PPN for a High or Critical Reliability system, or the EPN Maintenance circuit
pack in an EPN for the status of the battery pack and battery charger, and
reports the result. During this test, the status LED battery charger is lit and
extinguished if the status of the battery charger is reported as normal. This event
is a result of checking that the battery charger is connected.
Table 10-350. TEST #5 Battery & Battery Charger Query Test
Error
Code
Test
Result Description/ Recommendation
1000 ABORT System resources required to run this test are not available.
1. Retry the command at one-minute intervals a maximum of five times.
2. If the test continues to abort, escalate the problem.
1005 ABORT Battery Charger is not connected.
1. If the system has a UPS supplying the power, ignore this error since the
UPS supplies the power, not the battery and battery charger.
2. The batteries probably need charging and may be drained if there were
power outages. Reconnect the battery charger to allow the batteries to
recharge. If Test #5 is run before the batteries are completely charged, the
test fails.
3. Wait 24 hours and rerun the test.
2000 ABORT Response to the test request was not received within the allowable time
period.
1. Retry the command at one-minute intervals a maximum of five times.
2. If the test continues to ABORT with Error Code 2000, check for system
powering problems with the A carrier (PPN or EPN). Look for and resolve
all AC-POWER and CARR-POW alarms in a multicarrier cabinet system or
DC-POWER alarms in a single-carrier cabinet system. Repeat the test.
3. If the test continues to ABORT with a 2000 error code, check for and
resolve all DUPINT (Duplication Interface) errors in a Duplicated Option
PPN, PR-MAINT (Maintenance/Tape Processor) errors in a standard PPN,
or MAINT (EPN Maintenance circuit pack) errors in an EPN. Repeat the
test.
4. If the test continues to ABORT with a 2000 error code, escalate the
problem.
2028 ABORT Internal System Error prevented the extinguishing of the Battery Charger status
LED.
1. Retry the command at one-minute intervals a maximum of five times.
2. If the test continues to abort, escalate the problem.