DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si
555-230-127
Issue 1
August 1997
Maintenance Object Repair Procedures
Page 10-313CO-TRK (CO Trunk)
10
1000 ABORT System resources required to run this test are not available. The port may
be busy with a valid call. Use the display port PCSSpp command to
determine the trunk group/member number of the port. Use the status
trunk command to determine the service state of the port. If the service
state indicates that the port is in use, then the port is unavailable for certain
tests. (Refer to the "Status Commands" section in Chapter 10,
"Maintenance Commands and Trouble-Clearing Aids", for a full description
of all possible states.) You must wait until the port is idle before retesting.
1. If the port status is idle, then retry the command at one-minute
intervals a maximum of five times.
2. If the test continues to abort, escalate the problem.
1004 ABORT The port was seized by a user for a valid call. Use the display port
PCSSpp command to determine the trunk group/member number of the
port. Use the status trunk command to determine the service state of the
port. If the service state indicates that the port is in use, then the port is
unavailable for certain tests. You must wait until the port is idle before
retesting.
1. If the port status is idle, retry the command at 1 minute intervals for a
maximum of 5 times.
2. If the test continues to abort, escalate the problem.
1005 ABORT Test inapplicable to present configuration. This is a normal condition.
1018 ABORT Test has been disabled via administration.
1. Verify that the "Maintenance Tests?" field on the Trunk Group Form is
set to "n". To enable the test, issue the change trunk-group x
command where "x" equals the number of the trunk group to be
tested. Then change the entry in the "Maintenance Tests?" field on the
form to "y."
2000 ABORT Response to the request was not received within the allowable time period.
1. Retry the command at one-minute intervals a maximum of five times.
2. If the test continues to abort, escalate the problem.
Table 10-102. TEST #3 CO Demand Diagnostic Test — Continued
Error
Code
Test
Result Description/ Recommendation
Continued on next page