DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si
555-230-127
Issue 1
August 1997
Maintenance Commands and Trouble-Clearing Aids
Page 8-46display alarms
8
Feature Interactions
If the user disables the alarm origination with the change system
parameters-maintenance command, then the Ack? (Acknowledged)
field on the Alarm Report is blank regardless of the true acknowledged
state of the alarm.
Options screen
When you enter the display alarms command, the system first displays the
options screen. Select the options you want to view on the report. The figure
below is an example of the options screen for Alarm Reports.
1. Refer to the Report Scheduler and System Printer feature specification for more details.
Action/Object Qualifier Qualifier Description Permissions Defaults
Feature
Interactions
display alarms
print
schedule
Report sent to printer
Command is validated and then
a scheduling form displays to
schedule execution of the
command. The command is then
placed in the command queue
and is executed at the specified
time. The information displayed
by the command is sent to the
system printer instead of the
screen.
1
Examples:
display alarms
display alarms print
display alarms schedule
init
inads
craft
cust
rcust
bcms
browse
all alarms
displayed
See below
display alarms Page 1 of 1
ALARM REPORTS
The following options control which alarms will be displayed.
ALARM TYPES
Active? y_ Resolved? n_
Major? y_ Minor? y_ Warning? y_
REPORT PERIOD
Interval: m_ From: __/__/__:__ To: __/__/__:__
EQUIPMENT TYPE ( Choose only one, if any, of the following )
Cabinet: ____
Port Network: __
Board Number: _______
Port: ________
Category: ________
Extension: _____
Trunk ( group/member ): ___/___