DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si
555-230-127
Issue 1
August 1997
Maintenance Object Repair Procedures
Page 10-650EXT-DEV ADMIN? N (External Device Alarm)
10
System Technician-Demanded Tests:
Descriptions and Error Codes
Always investigate tests in the order presented in the table below when
inspecting errors in the system. By clearing error codes associated with the
Battery & Battery Charger Query Test,
you may also clear errors generated from
other tests in the testing sequence.
Notes:
a. Refer to POWER (Battery & Battery Charger) section for a description of
this test.
b. Refer to AC-POWER (AC Power) section for a description of this test.
c. Refer to CARR-POW (Carrier Port Power Supply) section for a description
of this test.
d. Refer to EMG-XFER (Emergency Transfer) section for a description of this
test.
e. Refer to CABINET (Cabinet Sensors) section for a description of this test.
1. D = Destructive; ND = Nondestructive
Multicarrier Cabinet Tests
Order of Investigation
Short Test
Sequence
Long Test
Sequence D/ND
1
Battery & Battery Charger Query Test (#5) (a) X X ND
AC Power Query Test (#78) (b) X X ND
OLS Query Test (Carrier E) (#127) (c) X X ND
OLS Query Test (Carrier D) (#127) (c) X X ND
OLS Query Test (Carrier A) (#127) (c) X X ND
OLS Query Test (Carrier B) (#127) (c) X X ND
OLS Query Test (Carrier C) (#127) (c) X X ND
Emergency Transfer Query Test (#124) (d) X X ND
Cabinet Sensors Query Test (#122) (e) X X ND
External Device Alarm Test (MAJOR port) (#120) X X ND
External Device Alarm Test (MINOR port) (#120) X X ND
Analog Ring Generator Initialization Test (#117) (f) X X ND
Analog Ring Generator Query Test (#118) (f) X X ND
Continued on next page