Lucent Technologies lucent Server User Manual


  Open as PDF
of 2392
 
DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si
555-230-127
Issue 1
August 1997
Maintenance Commands and Trouble-Clearing Aids
Page 8-194reset system
8
All successful reset system commands log users off.
Action/Object Qualifier Qualifier Description Permissions Defaults
Feature
Interactions
reset system
level
interchange
health-override
See below
Examples:
reset system 1
reset system 2
reset system
interchange
health-override
init
inads
craft
none see below
level
Reset levels are entered numerically:
1 = Warm Restart
2 = Cold-2
3 = Cold1
4 = Reboot
5 = Extended Reboot
interchange
System control passes to standby SPEs as active and standby SPEs
change roles. The optional “health-override” qualifier can be entered to
bypass Fault Severity Levels of standby SPEs to force an interchange.
SPE alarm components determine Fault Severity levels. Each
component is assigned a severity level, and the most severe SPE
alarm defines Fault Severity Levels for SPEs. The following table lists
maintenance objects, their alarms, severities and interchange restart
levels that affect SPE Fault Severity Levels.
Maintenance
Object Alarm Level
On/Off
Board
Fault
Severity Level
Restart
Level
STBY-SPE WARNING OFF 120 None
MEM-BD MAJOR or MINOR ON 110 Hot or Warm
MEMORY MAJOR or MINOR ON 110 Hot or Warm
STBY-SPE MAJOR ON 100 None
PROCR MAJOR ON 70 Hot or Warm
SW-CTL MAJOR ON 65 Cold 2
MEM-CARD MAJOR OFF 65 Cold 1
12V-PWR MIN ON 65 Hot
DUPINT MAJOR ON 61 Hot
CARR-POW MAJOR ON 61 Cold 2