Maintenance Object Repair Procedures
Page 10-277CARR-POW (Carrier Port Power Unit) for AC-Powered Systems
10
2000 ABORT Response to the test request was not received within the
allowable time period.
1. Retry the command at one-minute intervals a
maximum of five times.
2. If the test continues to ABORT with error code 2000,
check for system powering problems with the A
carrier (PPN or EPN). Look for and resolve all
AC-POWER and CARR-POW alarms in a multicarrier
cabinet system or DC-POWER alarms in a
single-carrier cabinet system. Then, repeat the test.
3. If the test continues to ABORT with a 2000 error
code, check for and resolve all DUPINT (Duplication
Interface) errors in a Duplicated Option PPN,
PR-MAINT (Maintenance/Tape Processor) errors in a
standard PPN, or MAINT (EPN Maintenance circuit
pack) errors in an EPN. Then, repeat the test.
4. If the test continues to ABORT with a 2000 error
code, escalate the problem.
2029 ABORT Internal System Error.
1. Retry the command at one-minute intervals a
maximum of five times.
2. If the test continues to abort, escalate the problem.
Table 10-83. TEST #127 Power Unit Query Test — Continued
Error
Code
Test
Result Description/ Recommendation
Continued on next page