DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si
555-230-123
Issue 1
April 1997
Maintenance Object Repair Procedures
Page 10-928MODEM-PT (Modem Pool Port)
10
Table 10-263. TEST #99 Modem Pool Audit Test
Error
Code
Test
Result Description/ Recommendation
NONE ABORT The system was not able to allocate all the necessary
resources to execute this test. An ABORT simply
indicates that the conversion resource was in use when
the audit was performed. No repair action is necessary
unless it was known that the conversion resource was
actually idle during the test (yellow in-use LED was off)
or was busied out before the test was run. If this is the
case, a TN758 failure condition may exist and the
following procedure should be used:
1. Busyout both of the TN758 Pooled Modem
conversion resources on the circuit pack containing
the failing conversion resource.
2. If the test continues to abort, replace the Pooled
Modem circuit pack and retest.
3. If the circuit pack fails after replacement, escalate
the problem.
Continued on next page