Page 10-522DIOD-TRK (DIOD Trunk) [G1.2SE]
10
1002 ABORT The system could not allocate time slots for the test. The
system may be under heavy traffic conditions or it may
have time slots out-of-service due to TDM-BUS errors.
Refer to TDM-BUS (TDM-Bus) Maintenance
documentation to diagnose any active TDM-BUS errors.
1. If system has no TDM-BUS errors and is not
handling heavy traffic, repeat test at one-minute
intervals a maximum of five times.
2. If the test continues to abort, escalate the problem.
1003 ABORT The system could not allocate a tone receiver for the
test. The system may be oversized for the number of
tone detectors present or some tone detectors may be
out-of-service.
1. Look for TTR-LEV errors in the Error Log. If present,
refer to TTR-LEV Maintenance documentation.
2. Look for TONE-PT errors in the Error Log. If present,
refer to TONE-PT Maintenance documentation.
3. If neither condition exists, retry the test at one-minute
intervals a maximum of five times.
4. If the test continues to abort, escalate the problem.
Table 10-141. TEST #6 NPE Crosstalk Test — Continued
Error
Code
Test
Result Description/ Recommendation