Lucent Technologies R5SI Computer Hardware User Manual


  Open as PDF
of 2643
 
DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si
555-230-123
Issue 1
April 1997
Maintenance Object Repair Procedures
Page 10-1252SPE-SELEC (SPE Select Switch)
10
Error Log Entries and Test to Clear Values
Notes:
a. The Warning alarm is upgraded to Major if the error is not resolved in six
hours.
b. Determine the carrier (a or b) by the Port field in the Error or Alarm Log.
For SPE-SELEC, the Port field is 1A (test duplication interface a) or 1B
(test duplication interface b).
System Technician-Demanded Tests:
Descriptions and Error Codes
Always investigate tests in the order presented in the table below. By clearing
error codes associated with the
Duplication Interface Circuit Pack Status Query
Test,
for example, you may also clear errors generated from other tests in the
testing sequence.
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
2. This error type initially raises a Warning alarm. If this error type persists and alarms are not
downgraded on this MO due to the values of set options, then, after a period of time, a Major alarm
is raised.
Table 10-389. SPE Select Switch Error Log Entries
Error
Type
Aux
Data Associated Test
Alarm
Level
On/Off
Board Test to Clear Value
0
1
0 Any Any Any test duplication-interface 1C
sh r 1
1 Any SPE Select Query
Test (#278)
WARNING/
MAJOR
2
OFF test duplication-interface 1C
sh r
257 any SPE Select Query
Test (#278)
WARNING/
MAJOR
2
OFF test duplication-interface 1C
sh r 2
Order of Investigation
Short Test
Sequence
Long Test
Sequence D/ND
1
Duplication Interface Circuit Pack Status Query Test
(#315) (a)
XXND
Duplication Interface Circuit Pack Sanity Circuit Test
(#273) (a)
XD
Continued on next page