DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si
555-230-123
Issue 1
April 1997
Maintenance Object Repair Procedures
Page 10-956M/T-ANL (Maintenance/Test Analog Port)
10
Analog Port Digital Loop Around Test (#13)
This test is a modification of the Voice and Control Channel Local Loop Test used
by Digital Station (DIG-LINE) maintenance. This test does not perform the control
channel and secondary information channel loop around tests as described for
DIG-LINE, as these data paths do not exist for the Maintenance/Test Analog Port.
The primary information channel is tested by first looping back the data channel
onto the TDM Bus, and then sending a digital count from the Tone-Clock circuit
pack and receiving the same digital count with a general purpose tone detector.
A conference test is done next for the primary information channel. This test is the
same as Conference Test (#6).
Only one value (Pass, Fail, or Abort) is generated as a result of the two tests. If
either fails or aborts, the sequence is stopped
Table 10-274. TEST #13 Analog Port Digital Loop Around Test
Error
Code
Test
Result Description/ Recommendation
ABORT Internal System Error
1. Retry the command at 1 minute intervals a maximum
of 3 times.
2. If the test continues to abort, escalate the problem.
1000 ABORT The port is in use on a valid ATMS Test Call.
1. Retry the command at 1 minute intervals a maximum
of 3 times.
2. If the test continues to abort and the port is not in
use on a valid ATMS Test Call, escalate the problem.
To determine whether the port is in use by an ATMS
Test Call enter status station ext where ext is the
assigned ATMS station number.
1001 ABORT System resources required to run this test are not
available.
1. Retry the command at 1 minute intervals a maximum
of 3 times.
2. If the test continues to abort, escalate the problem.
Continued on next page