Lucent Technologies R5SI Computer Hardware User Manual


  Open as PDF
of 2643
 
DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si
555-230-123
Issue 1
April 1997
Maintenance Object Repair Procedures
Page 10-638EMG-XFER
10
Error Log Entries and Test to Clear Values
System Technician-Demanded Tests:
Descriptions and Error Codes
Always investigate tests in the order presented in the following tables. By
clearing error codes associated with the
Battery & Battery Charger Query Test,
for example, you may also clear errors generated from other tests in the testing
sequence. For example, you may also clear errors generated from other tests in
the testing sequence.
Single Carrier System
Notes:
a. Refer to “DC-POWER” for a description of this test.
b. Refer to “EXT-DEV” for a description of this test.
c. Refer to “RING-GEN” for a description of this test.
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
1. D = Destructive; ND = Nondestructive
Table 10-184. Emergency Transfer Error Log Entries
Error
Type
Aux
Data Associated Test
Alarm
Level
On/Off
Board Test to Clear Value
0
1
0 Any Any Any test environment P sh r 1
1 Any Emergency Transfer
Query (#124)
MAJOR ON test environment P r 3
257 0 Emergency Transfer
Query (#124)
WARNING ON test environment P r 3
Order of Investigation
Short Test
Sequence
Long Test
Sequence D/ND
1
Power Query Test (#79) (a) X X ND
Emergency Transfer Query Test (#124) X X ND
External Alarm Lead Query Test (#120) (b) X X ND
Analog Ring Generator Initialization Test (#117) (c) X X ND
Analog Ring Generator Query Test (#118) (c) X X ND