DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si
555-230-123
Issue 1
April 1997
Maintenance Object Repair Procedures
Page 10-357CO-TRK (CO Trunk)
10
1906 ABORT Reorder tone detected from far end.
1. See actions for error code 1905.
1907 ABORT Other unexpected tone detected from far end.
1. See actions for error code 1905.
1913 ABORT Audible Ring detected from far end.
1. See actions for error code 1905.
1914 ABORT Unidentified interrupted tone detected from far end.
1. See actions for error code 1905
1915 ABORT Busy tone detected from far end.
1. Since the test line at the far end was busy. Try the
test again.
2. If the test continues to abort, the problem is with the
far end system.
1918 ABORT Test progress tone not removed from far end (type 105
test line only).
1. The problem is with the far end system; a technician
at the far end should test the test line (TN771 or
ADFTC).
1919 ABORT Unexpected far end release
1. The problem is with the far end system; a technician
at the far end should test the test line (TN771 or
ADFTC).
1920 ABORT No response from far end.
1. The problem is with the far end system; a technician
at the far end should test the test line (TN771 or
ADFTC).
1921 ABORT No data returned from far end.
1. The problem is with the far end system; a technician
at the far end should test the test line (TN771 or
ADFTC).
Table 10-99. TEST #844-848 Transmission Test — Continued
Error
Code
Test
Result Description/ Recommendation
Continued on next page