DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si
555-230-123
Issue 1
April 1997
Maintenance Object Repair Procedures
Page 10-712EXT-DEV ADMIN? N (External Device Alarm)
10
ANY FAIL The External Device Alarm has been activated by the
external device.
1. Clear the major alarm on the external device, and
rerun the test.
2. If the test still fails, then disconnect the External
Device Alarms from the Maintenance circuit pack
and rerun the test.
3. If the test still fails, then there is a problem with the
Maintenance circuit pack that is reporting the alarm.
This circuit pack should be replaced. There are
failures that can occur on Maintenance circuit
pack’s that
will not
be detected by their respective
maintenance, but which will cause many
environment tests to fail. If many environment tests
are failing, the suspect circuit pack should be
replaced and the test rerun.
4. If the test still fails, escalate the problem.
PASS If there is a problem with the external device, but the
Maintenance circuit pack connected to the device
reports no alarm, then the External Device may not be
properly reporting the problems or the External Device
may not be properly connected to the External Device.
Table 10-201. TEST #120 External Device Alarm Test — Continued
Error
Code
Test
Result Description/ Recommendation
Continued on next page