DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si
555-230-123
Issue 1
April 1997
Maintenance Commands and Trouble-Clearing Aids
Page 8-403status card-mem
8
Defaults
None.
Parameters
Help Messages
If the system technician presses HELP after entering "status card-mem," the
following message is displayed for a duplex system:
Enter [cabinet(1)];carrier(A-B), [’print’]
[’print’]
Error Messages
If the carrier entered is invalid, the following message will be displayed:
"entered value" is an invalid identifier;
press RETURN to execute modified command
If the NETCON board is not TN777B, then the following message will be
displayed:
Must install TN777B circuit pack
If the system is insane, the following message will be displayed:
Error encountered, can’t complete request
If the command entered is in conflict with another currently executing command,
then a message will be displayed showing the login id of the conflicting user and
the conflicting command. The message is as follows:
’login id’:’command’ has a command conflict
If the standby is entering maintenance mode when this command is executed,
then the following message is displayed:
Cannot interrupt Standby SPE while entering
maintenance mode; please try later
If the standby SPE is not refreshed when this command is executed, then the
following message is displayed:
location This parameter indicates the carrier location where the memory card
resides in a High or Critical Reliability System. This field is not required
in a simplex switch configuration. In a duplex switch configuration, this
field is required and it can be either "A" for control carrier A in
Processor Port Network (PPN) or "B" for control carrier B in PPN.
print Print the status on the printer attached to the SAT.