DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si
555-230-123
Issue 1
April 1997
Maintenance Commands and Trouble-Clearing Aids
Page 8-580test environment
8
test environment
This command will test the environment monitoring and control capabilities
including emergency transfer in any cabinet.
Synopsis
test environment location
[ short | long ][ repeat number | clear ] schedule
Permissions
The following default logins may execute this command: system technician,
inads, init.
Examples
test environment
test environment schedule
test environment 1 sh
test environment 1 l r 25
test environment 01 l r 25
test environment 01 l r 25 schedule
test environment 2 l c
test environment 3 c
Description
The test environment command performs hardware diagnostic tests of the
environment monitoring and control, and emergency transfer functions of a
technician specified cabinet. This command will test both Processor Port
Network (PPN) cabinets and Expansion Port Network (EPN) cabinets. Circuit
packs involved are the Processor circuit pack (PPN simplex systems), the
Duplication Interface circuit pack (PPN duplex systems) and EPN Maintenance
circuit packs. The tone/clock circuit pack is involved in tests of the ring
generator.
There are 8 Maintenance Objects involved in this testing. DC-POWER tests
power availability, battery charging and temperature functions in SCC cabinets
only. EMG-XFER tests emergency transfer status, and EXT-DEV tests external
(i.e. AUDIX) alarm status for both the SCC and MCC cabinet systems. POWER
tests battery backup, AC-POWER tests AC power availability, CARR_POW tests
carrier DC power availability, CABINET tests air flow and temperature, RING_
GEN tests ringing voltage are tested in MCC cabinets only.
Note that the long test of CARR_POW includes a power recycle test for
non-Processor Element (SPE) carriers and is destructive. There is one instance of
CARR_POW for each carrier in the cabinet.