DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si
555-230-123
Issue 1
April 1997
Maintenance Object Repair Procedures
Page 10-533DS1-BD (DS1 Interface Circuit Pack)
10
Notes:
a. This error indicates that the circuit pack has stopped functioning or is not
completely administered. The alarm is logged about 15 minutes after the
circuit pack has been removed or 11 minutes after the SAKI Test (#53)
fails.
To be completely administered, a DS1 circuit pack must meet all 3 of the
following conditions:
1. Have an entry in the circuit plan via the change circuit pack
command
2. Be administered via the add ds1 PCSS command
3. Be physically inserted in the appropriate slot
If the circuit pack has an entry in the circuit plan and either of the other two
conditions are
not
met, a MINOR alarm is logged. To resolve the error
either
1. Make sure all conditions for administration are met and that a
functioning DS1 circuit pack is inserted in the correct slot.
2. Completely remove the DS1-BD from the system using the following
steps:
a. Remove any administered DS1 trunks or access endpoints
associated with the circuit pack from their trunk groups.
b. Execute the remove ds1 PCSS and change circuit pack
PCSS commands.
If all the administration conditions are met for this circuit pack and the red
LED is still on, follow the instructions for
LED Alarms with Error Type 1
in
Chapter 7.
b. The DS1 Interface circuit pack has been busied out by a busy-out board
PCSS command.
c. The DS1-BD circuit pack is not completely administered. A completely
administered DS1-BD circuit pack should have an entry in the circuit plan
via the change circuit pack command, should have been administered
via the add ds1 PCSS command, and should have been inserted into the
appropriate port slot.
d. The circuit pack in the slot does not match the type administered to that
position. Either replace the circuit pack with one of the type administered,
or use change circuit-pack to readminister the slot. This error may also
indicate that the 24/32-channel selection on the DS1 administration form
does not match the configuration of the circuit pack.
e. This error is associated with the Common Port Circuit Pack Maintenance
Test. Refer to "XXX-BD (Common Port Circuit Pack)" for details.
f. The DS1 Interface circuit pack has detected a transient hardware problem
(for example, external RAM failure, internal RAM failure, internal ROM
failure, or instruction set failure). This error will disappear when no faults