Lucent Technologies R5SI Computer Hardware User Manual


  Open as PDF
of 2643
 
DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si
555-230-123
Issue 1
April 1997
Maintenance Object Repair Procedures
Page 10-730FL-DATA (Flash Data Consistency)
10
81 FAIL The update files, translations, and announcements are different in
both SPEs. The Active SPE has the most current translations, and the
Standby SPE has the most current update file and announcements.
82 FAIL The update files, translations, and announcements are different in
both SPEs. The Standby SPE has the most current update file,
translations, and announcements.
1. Issue the save translations command.
2. Issue the save announcements command.
3. Follow the procedures for Error Code 64.
84 FAIL The update files, load vintages, and announcements are different in
both SPEs. The Standby SPE has the most current update file and
announcements.
85 FAIL The update files, load vintages, translations, and announcements are
different in both SPEs. The Active SPE has the most current
translations, and the Standby SPE has the most current update file
and announcements.
86 FAIL The update files, load vintages, translations, and announcements are
different in both SPEs. The Standby SPE has the most current update
file, translations, and announcements.
1. Follow the procedures for Error Code 4 to correct the load
vintage. After running the test card-mem long command, check
for Error Codes 32 or 64. Follow the recovery procedure under
the applicable error code.
Table 10-205. TEST #421 Flash Data Consistency Check Test — Continued
Error
Code
Test
Result Description/Recommendation
Continued on next page