DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si
555-230-123
Issue 1
April 1997
Maintenance Object Repair Procedures
Page 10-1129POWER (Battery & Battery Charger) for AC-Powered Systems
10
4 FAIL The battery is currently being charged at the high
charge rate.
1. After 30 hours, the battery should be fully charged,
and this error should disappear.
2. If after 30 hours the battery is still in the high charge
rate, an alarm is raised. Display the Error Log with
the display errors command and select the
category "environ" to display only
environment-related errors. Look for POWER errors
of type 257. The FIRST OCCURRENCE of this error
indicates the time when the battery started charging.
Use this time as the starting point to determine if the
battery has been charging for 30 hours. If the battery
has been charging for 30 hours, then replace the
battery.
!
CAUTION:
Read the section, ‘‘Replacing the Battery and
Battery Charger’’ before proceeding.
Table 10-332. TEST #5 Battery & Battery Charger Query Test — Continued
Error
Code
Test
Result Description/ Recommendation
Continued on next page