DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si
555-230-123
Issue 1
April 1997
Maintenance Object Repair Procedures
Page 10-1137POWER (Battery & Battery Charger for DC-Powered Systems
10
any FAIL The Duplication Interface circuit pack in a PPN for a high or critical
reliability system is incorrectly reporting a problem with power. If this test
fails, the problem is with the circuit pack and not with POWER.
1. The suspect circuit pack, depending on the system configuration,
should be replaced and the test rerun.
PASS All that can be inferred is that the DUPINT (Duplication Interface) circuit
pack in a PPN for a high or critical reliability system is working properly.
Table 10-334. TEST #5 Battery & Battery Charger Query Test — Continued
Error
Code
Test
Result Description/ Recommendation
Continued on next page