DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si
555-230-123
Issue 1
April 1997
Maintenance Object Repair Procedures
Page 10-1678XXX-BD (Common Port Circuit Pack)
10
SAKI Sanity Test (#53)
This test is destructive.
This test resets the circuit pack.
FAIL The test failed because the circuit pack failed to return
the circuit pack code or vintage.
1. Retry the command for a maximum of 5 times.
2. If the test still fails, issue the busyout board, reset
board, and release busy board commands, and
then retest.
3. If the problem continues, replace the circuit pack.
4. Run the test again.
5. If the test continues to fail, escalate the problem.
PASS Communication with this circuit pack is successful.
EXTRA BD This result should only appear for the TN771B or
TN771C Maintenance/Test circuit pack. More than one
circuit pack has been installed in this port network.
Remove this circuit pack.
any NO
BOARD
This is normal if the test is being done when (a) the
circuit pack is not physically in the system or (b) the
system is booting up. Otherwise, there is some
inconsistency between the physical configuration and
the data kept in the system.
1. Verify that the circuit pack is physically in the
system.
2. Verify that the system is not in a stage of booting up.
3. ) Retry the command at one-minute intervals for a
maximum of five times.
4. If the test continues to return NO BOARD, escalate
the problem.
Table 10-494. TEST #52 Control Channel Loop Around Test — Continued
Error
Code
Test
Result Description/ Recommendation
Continued on next page