DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si
555-230-123
Issue 1
April 1997
Maintenance Object Repair Procedures
Page 10-1228SHDW-CIR (Common Shadow Circuit)
10
Error Log Entries and Test to Clear Values
System Technician-Demanded Tests:
Descriptions and Error Codes
Always investigate tests in the order they are presented in the table below. By
clearing error codes associated with the
Duplication Interface Circuit Pack Status
Query Test,
for example, you may also clear errors generated from other tests in
the testing sequence.
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
Table 10-383. Common Shadow Circuit Error Log Entries
Error
Type
Aux
Data Associated Test
Alarm
Level
On/Off
Board Test to Clear Value
0
1
0 Any Any Any test duplication 1C sh r 1
1 Common Shadow
Circuit Loop Back Test
(#283)
MAJOR ON test duplication 1C r 3
257 Any Common Shadow
Circuit Time-Out Query
Test (#285)
MAJOR OFF test duplication 1C l r 3
513 1,2 Common Shadow
Circuit Address
Decoder Test (#284)
MAJOR ON test duplication 1C r 3
Order of Investigation
Short Test
Sequence
Long Test
Sequence D/ND
1
Duplication Interface Circuit Pack Status Query Test
(#315) (a)
XXND
Duplication Interface Circuit Pack Sanity Circuit Test
(#273) (a)
XD
Duplication Interface Circuit Pack Sanity Maze Test
(#277) (a)
XXND
Duplication Interface Circuit Pack SPE A Loop Back Test
(#275) (a)
XXND
Duplication Interface Circuit Pack SPE B Loop Back Test
(#276) (a)
XXND
Continued on next page