DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si
555-230-123
Issue 1
April 1997
Maintenance Object Repair Procedures
Page 10-1124POWER (Battery & Battery Charger) for AC-Powered Systems
10
5. Check the battery dates and replace the batteries if they are more than
four years old or if a POWER alarm is present.
NOTE:
If any defective batteries are found, replace all of them. Batteries are
ordered in sets of three and should be replaced as such.
6. If no defective batteries are found, replace the entire charger.
7. Close the cover and secure it with the screw.
8. Reconnect the cord and move the power switch to ON.
Hardware Error Log Entries and Test to Clear
Values
a. Where P is an appropriate port network number determined via the Port
field from the Alarm or Error Log.
System Technician-Demanded Tests:
Descriptions and Error Codes
Always investigate tests in the order presented in the table below when
inspecting errors in the system. By clearing error codes associated with the
Battery & Battery Charger Query Test,
for example, you may also clear errors
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
Battery & Battery Charger Error Log Entries
Error
Type
Aux
Data Associated Test
Alarm
Level
On/Off
Board Test to Clear Value
0
1
0 Any Any Any test environment P sh r 1
1 Any Battery & Battery
Charger Query Test
(#5) (Error Code 8)
MINOR ON test environment P sh r 1
257 Any Battery & Battery
Charger Query Test
(#5) (Error Code 4)
MINOR ON test environment P sh r 1
769 Any Battery & Battery
Charger Query Test
(#5) (Error Code 2)
MINOR ON test environment P sh r 1
3840 1005
or
1028
Battery & Battery
Charger Query Test
(#5)
ON test environment P sh r 1