Maintenance Commands and Trouble-Clearing Aids
Page 8-583test environment
8
For the following output example, assume that the command that was entered
was "test environment 2" where cabinet 2 is an SCC cabinet.
Feature Interactions
The long test will recycle power in some specified cabinet on non-SPE and
maintenance board carriers and is destructive. Specifically, the ’a’ carrier of
PPNs and EPNs does not have power recycled. In PPNs containing duplicated
SPEs the ’b’ carrier also does not have power recycled.
All port carriers are recycled, and service is interrupted for each port carrier. If a
carrier containing an active EI is recycled, communications with that cabinet will
be disrupted. If a carrier containing an active tone-clock board is recycled, all
ports in the cabinet or port network will have service disrupted.
test environment 1
TEST RESULTS
Port Maintenance Name Alt. Name Test No. Result Error Code
01 POWER 5 PASS
01 AC-POWER 79 PASS
01A CARR-POW 127 PASS
01B CARR-POW 127 PASS
01C CARR-POW 127 PASS
01D CARR-POW 127 PASS
01E CARR-POW 127 PASS
01 EMG-XFER 124 PASS
01 CABINET 122 PASS
01 EXT-DEV 120 PASS
01 RING-GEN 118 PASS
Command Successfully Completed
test environment 2
TEST RESULTS
Port Maintenance Name Alt. Name Test No. Result Error Code
02 DC-POWER 5 PASS
02 EMG-XFER 124 PASS
02 EXT-DEV 120 PASS
02 RING-GEN 117 PASS
02 RING-GEN 118 PASS
Command Successfully Completed