DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si
555-230-123
Issue 1
April 1997
Maintenance Object Repair Procedures
Page 10-1292STBY-SPE (Standby SPE)
10
2051 ABORT When attempting to refresh Standby SPE memory from Active SPE memory,
the Active SPE could not determine the status of one of the Duplication
Interface circuit packs, or it determined that one of the Duplication Interface
circuit packs was defective.
1. Check for carrier A Duplication Interface circuit pack errors and alarms.
Refer to DUPINT (Duplication Interface Circuit Pack) Maintenance
documentation and follow the prescribed procedures.
2. Check for carrier B Duplication Interface circuit pack errors and alarms.
Refer to DUPINT (Duplication Interface Circuit Pack) Maintenance and
follow the prescribed procedures.
3. Check the Inter-Carrier Cable to see if the cable is loose or disconnected.
If so, follow the repair procedures for reconnecting the Inter-Carrier Cable
described in Chapter 6, ‘‘
Reliability Systems: A Maintenance Aid’’.
4. If all problems found in Steps 1, 2, and 3 have now been repaired,
proceed with Step 8. If no problems were found in Steps 1, 2, and 3,
proceed with Step 5.
5. Issue the display errors command and check to see if Error Type 80 is
logged against STBY-SPE. If so, the problem is the carrier A Duplication
Interface circuit pack. Replace the carrier A Duplication Interface circuit
pack as described in Chapter 6, ‘‘
Reliability Systems: A Maintenance Aid’’
and proceed with Steps 8, 9, and 10.
6. Issue the display errors command and check to see if Error Type 82 is
logged against STBY-SPE. If so, the problem is the carrier B Duplication
Interface circuit pack. Replace the carrier B Duplication Interface circuit
pack as described in Chapter 6, ‘‘
Reliability Systems: A Maintenance Aid’’
and proceed with Steps 8, 9, and 10.
7. If Error Type 80 or 82 is not logged, escalate the problem.
2051
(cont’d.)
ABORT 8. Issue the refresh spe-standby command to put the Standby SPE in
Standby Mode. This command may have to be issued multiple times. If the
refresh spe-standby command successfully completes five times without
the Standby SPE becoming labeled "standby" on the status system form,
wait 20 minutes. This does not include cases where the command
completes with the terminal message line errors "Refresh not successful;
use ‘display errors’ to check for STBY-SPE errors" or "Cannot interrupt
Standby SPE while entering maintenance mode; please try later." Issue the
refresh spe-standby command once more.
9. Repeat the test.
10. Issue the test spe-standby long command to thoroughly test all Standby
SPE components.
Table 10-392. Test Result Error Codes Associated with the Standby SPE
Continued
Error
Code
Test
Result Description/ Recommendation
Continued on next page