Maintenance Object Repair Procedures
Page 10-1469TIE-TRK (Tie Trunk)
10
1040 ABORT (Non-TN497 circuit packs only.) This test is not
performed for trunk ports administered as access
endpoints.
1. Verify this port is an access endpoint by using the
display port command.
2. If the port has been administered as an access
endpoint, this test should abort.
2000 ABORT Seizure message is not received back within 10
seconds.
1. Retry the command at one-minute intervals a
maximum of five times.
2. If the test continues to fail, check the far-end PBX to
ensure a translation match at both ends.
3. Check the facility.
2100 ABORT Could not allocate the necessary system resources to
run the test. This could be due to a failure to seize the
port.
1. Retry the command at 1-minute intervals a maximum
of 5 times.
2. If the test continues to abort, escalate the problem.
3 FAIL (TN439 circuit packs only.) No dial tone detected from
the other end.
1. Retry the command at one minute intervals a
maximum of five times.
2. If the test continues to fail, check the far-end PBX to
ensure a translation match at both ends.
3. Check the facility.
PASS The relevant seizure test passes. This port is functioning
properly.
1. If users are reporting troubles, examine loop
connections to the port, wiring, and stations.
Table 10-445. Seizure Tests (#73, #747, #73) — Continued
Error
Code
Test
Result Description/ Recommendation
Continued on next page